Dwyer 605-3

Dwyer Magnehelic Series 605 Differential Pressure Indicating Transmitter User Manual

Model: 605-3 | Range: 0-3.0"WC

හැඳින්වීම

The Dwyer Magnehelic Series 605 Indicating Transmitter is designed for both visual monitoring and electronic control of very low differential pressure. This device is suitable for control applications in building HVAC systems, providing local indication for routine maintenance and system troubleshooting. It combines the reliable Dwyer Magnehelic gauge mechanical design with Series 600 transmitter technology, offering a two-wire, 4-20 mA control signal. The terminal strip on the rear simplifies connection to any 4-20 mA control loop powered by a 10-35 VDC supply.

Dwyer Magnehelic Series 605 Differential Pressure Indicating Transmitter front view

රූපය 1: ඉදිරිපස view of a Dwyer Magnehelic Indicating Transmitter. The dial displays pressure in inches of water, with a visible range from 0 to 1.0. The face includes the "Magnehelic" brand, "Indicating Transmitter" label, maximum pressure rating (25 PSIG), and patent information. Adjustment screws for "SPAN" and "ZERO" are visible at the bottom, along with the Dwyer logo. Note that the specific model 605-3 covered in this manual has a 0-3.0"WC range.

ආරක්ෂිත තොරතුරු

Read this manual thoroughly before installing, operating, or servicing this device. Failure to follow these instructions may result in product damage, property damage, or serious injury. Keep this manual for future reference.

පිරිවිතර

පරාමිතියවටිනාකම
ආදර්ශ අංකය605-3
පීඩන පරාසය0-3.0"WC (Inches of Water Column)
ප්රතිදාන සංඥාව4-20 mA, 2-wire
බල සැපයුම10-35 VDC
උපරිම පීඩනය25 PSIG
නිෂ්පාදන මානයන්අඟල් 7.6 x 6.8 x 3.7
බරපවුම් 2.35ක්
නිෂ්පාදකයාඩුවර් උපකරණ

සැකසුම සහ ස්ථාපනය

සවි කිරීම

The Series 605 can be flush mounted or surface mounted. Ensure the mounting location is free from excessive vibration and within the specified operating temperature range. The device should be mounted vertically for accurate readings.

  1. සවි කිරීම සඳහා සුදුසු ස්ථානයක් තෝරන්න.
  2. Secure the transmitter using appropriate hardware (not included).
  3. Ensure the pressure ports are accessible for tubing connections.

පීඩන සම්බන්ධතා

Connect the pressure tubing to the high and low pressure ports located on the back of the unit. Use appropriate tubing and fittings for the application. The high pressure port is typically marked "HIGH" or "+", and the low pressure port "LOW" or "-".

විදුලි රැහැන්

The Series 605 utilizes a two-wire, 4-20 mA output. Connect the transmitter to a 10-35 VDC power supply and the control system as follows:

මෙහෙයුම

පවර් ඔන්

Once all connections are secure, apply power to the unit. The analog output will begin to transmit a 4-20 mA signal corresponding to the measured differential pressure.

සංදර්ශකය කියවීම

The Magnehelic gauge provides a local visual indication of the differential pressure. The red pointer on the dial indicates the current pressure in inches of water column ("WC").

Zero සහ Span ගැලපීම

The Series 605 features external zero and span adjustments. These adjustments affect both the visual indication and the 4-20 mA output.

  1. ශුන්‍ය ගැලපීම: With no pressure applied (both ports open to atmosphere or connected to the same pressure), adjust the "ZERO" screw (typically located at the bottom right of the dial) until the pointer reads 0"WC. This also calibrates the 4 mA output.
  2. පරතරය ගැලපීම: Apply a known full-scale pressure (e.g., 3.0"WC for a 0-3.0"WC range). Adjust the "SPAN" screw (typically located at the bottom left of the dial) until the pointer reads the full-scale value. This calibrates the 20 mA output. Repeat zero and span adjustments as necessary for optimal accuracy.

නඩත්තු කිරීම

The Dwyer Magnehelic Series 605 is designed for minimal maintenance. Regular checks ensure continued accuracy and reliable operation.

දෝෂගවේෂණය

ගැටලුවවිය හැකි හේතුවවිසඳුම
No Indication / No OutputNo power; Incorrect wiring; Blocked pressure ports; Damaged unit.Check power supply (10-35 VDC); Verify wiring connections and polarity; Inspect pressure ports and tubing for obstructions; Contact technical support if unit is damaged.
වැරදි කියවීම්Out of calibration; Leaks in pressure lines; Incorrect mounting position; Environmental factors.Perform zero and span calibration; Check all pressure connections for leaks; Ensure unit is mounted vertically; Verify operating environment.
Output Signal Stuck at 4 mA or 20 mASensor fault; Wiring issue; Over-range/Under-range pressure.Check pressure applied is within range; Verify wiring integrity; Contact technical support.

වගකීම් සහ සහාය

Dwyer Instruments, Inc. warrants this product to be free from defects in material and workmanship for a period of one year from the date of shipment. For full warranty details, technical support, or service, please contact Dwyer Instruments directly. Contact information can be found on the official Dwyer webඅඩවිය.

Dwyer Instruments, Inc.
Michigan City, IN 46360 U.S.A.
www.dwyer-inst.com

අදාළ ලියකියවිලි - 605-3

පෙරview ඩ්වයර් මැග්නහෙලික්® අවකල පීඩන මානය (HP/MP) - පිරිවිතර සහ උපදෙස්
Dwyer's Magnehelic® ඉහළ සහ මධ්‍යම පීඩන අවකල පීඩන මාපක (Bulletin A-27-HP-MP) සඳහා තාක්ෂණික පිරිවිතර, ස්ථාපනය සහ මෙහෙයුම් උපදෙස්. ආකෘති විස්තර, නිරවද්‍යතාවය, උෂ්ණත්ව පරාසය, සවි කිරීම, සම්බන්ධතා සහ උපාංග ඇතුළත් වේ.
පෙරview ඩ්වයර් මැග්නහෙලික් අවකල පීඩන මාපක බුලටින් A-27
විවිධ මාදිලි සඳහා පිරිවිතර, ස්ථාපනය, ක්‍රියාකාරිත්වය සහ දෝශ නිරාකරණය ඇතුළුව, ඩ්වයර් මැග්නහෙලික් අවකල පීඩන මානය විස්තර කරන තාක්ෂණික ප්‍රකාශනය.
පෙරview ඩ්වයර් ක්‍රියාවලි ස්වයංක්‍රීයකරණ නිෂ්පාදන යෙදුම් සහ තේරීම් මාර්ගෝපදේශ
Explore Dwyer Instruments' comprehensive guide to process automation, covering product applications and selection for HVAC, water treatment, oil & gas, and more. Discover instrumentation solutions for pressure, flow, level, temperature, and air quality.
පෙරview ඩ්වයර් මැග්නහෙලික් අවකල පීඩන මානය - බුලටින් A-27
Dwyer Magnehelic අවකල පීඩන මාපක, 2000 මාලාව සඳහා තාක්ෂණික පිරිවිතර, ස්ථාපන මාර්ගෝපදේශය, ක්‍රියාකාරිත්වය සහ දෝශ නිරාකරණය.
පෙරview Dwyer Series 616KX අවකල පීඩන සම්ප්‍රේෂක පරිශීලක මාර්ගෝපදේශය
Dwyer Series 616KX අවකල පීඩන සම්ප්‍රේෂකය සඳහා පරිශීලක මාර්ගෝපදේශය, ස්ථාපනය, පිරිවිතර, විදුලි සම්බන්ධතා, ක්‍රියාකාරිත්වය, ශුන්‍ය ගැලපීම, ප්‍රතිදාන සංඥා වින්‍යාසය, පූර්වාරක්ෂාවන්, නඩත්තුව සහ වගකීම් තොරතුරු විස්තර කරයි.
පෙරview ඩ්වයර් ශ්‍රේණි ඩීඑම් ඩිජිමැග් ආන්තර පීඩන සම්ප්‍රේෂක ඉක්මන් ආරම්භක මාර්ගෝපදේශය
Dwyer Series DM DigiMag අවකල පීඩන සම්ප්‍රේෂකය සඳහා ඉක්මන් ආරම්භක මාර්ගෝපදේශය, සවි කිරීම, රැහැන් ඇදීම සහ ක්‍රමාංකනය සඳහා අත්‍යවශ්‍ය තොරතුරු සපයයි.